|
EXAMPLE PROBLEM (REVERBERATION TIME)
A classroom 60 ft long by 35 ft wide by 15 ft high has sound absorption
coefficients α of 0.30 for walls, 0.04 for ceiling, and 0.10 for floor.
All α are at 500 Hz.
Find the reverberation time T at 500 Hz in this space with no occupants
and no sound-absorbing treatment.
1. Compute the room volume V.
V=60X35X15=31,500ft
2. Compute the surface areas S.
Ceiling S =60X35=2100ft
Walls S = 2 X 35 X 15 = 1050 ft
S = 2X60X 15= 1800ft
Floor S = 60 X 35 = 2100 ft
3. Compute the total room absorption a using a = Σ S α .
|
S |
α |
a (sabins) |
Ceiling
Walls
Floor |
2100 X
2850 X
2100 X |
0.04 =
0.30 =
0.10= |
84
855
210 |
Total a = 1149 sabins
Note: Include air absorption in total for large rooms at frequencies
greater than 1000 Hz.
4. Compute the reverberation time T using T = 0.05 (V/a)
T = 0.05 (V÷a) = 0.05 X 31,500÷1149 = 1575÷1149 = 1.37s at 500 Hz
Find the reverberation time T if 50 percent of the ceiling surface
(along the perimeter of the room) is treated with acoustical panels
at α of 0.85. The central area remains sound-reflecting to help distribute
sound energy from lectern end toward rear of the room.
1. Compute the total room absorption a using a = Σ S α.
|
S |
α |
a (sabins) |
Bare ceiling
Treated ceiling
Walls
Floor |
1050x0.04=
1050x0.85=
2850x0.30=
2100x0.10= |
|
42
892
855
210 |
Total a = |
1999 sabins |
2. Compute new reverberation time T.
T = 0.05 (V÷a) = 0.05x31,500÷1999 = 1575÷1999 = 0.79s at 500Hz
The reverberation time is reduced to below 1 s with 50 percent ceiling
treatment for unoccupied conditions. This represents a reduction of
(1.37 - 079)/1.37 x 100 = 42 percent, which is a “clearly noticeable
change. Absorption provided by teachers and students will further
reduce reverberation depending on the number of occupants, their distribution
throughout the room, and the clothing worn.
HOW TO COMPUTE SURFACE AREAS
To find total absorption in a room, first compute the surface areas
of ceiling, walls, and floor and then multiply by their respective
sound absorption coefficients. Next, add absorption from occupants
and furnishings. A wide variety of surface shapes, along with corresponding
formulas to find area, are shown below. Areas of irregular shapes
can be found by subdividing the surface into smaller areas of equal
widths. The more divisions by parallel lines, the greater the accuracy.
For alternate methods to compute areas of irregular shapes, see p.
667 in J. N. Boaz (ed.), Architectural Graphic Standards, Wiley, New
York, 1970.
Note: For a review of trigonometry, see pp. 144-145 in M. D. Egan,
Concepts in Architectural Lighting, McGraw-Hill, 1983. A comprehensive
self-study review of mathematics for architecture is presented by
M. Salvadori, Mathematics in Architecture, Prentice-Hall, Englewood
Cliffs, N.J., 1968.
The buildup of sound levels in a room is due to the repeated reflections
of sound from its enclosing surfaces. This buildup is affected by
the size of the room and the amount of absorption within the room.
The difference in decibels in reverberant noise levels, or noise reduction,
under two conditions of room absorption can be found as follows:
NR = 10 log (a2÷a1)
ROOM NOISE REDUCTION
The buildup of sound levels in a room is due to the repeated reflections
of sound from its enclosing surfaces. This buildup is affected by
the size of the room and the amount of absorption within the room.
The difference in decibels in reverberant noise levels, or noise reduction,
under two conditions of room absorption can be found as follows:
NR = 10 log = (a2÷a1)
where NR = room noise reduction (dB)
a1 = total room absorption after treatment (sabins)
a2 = total room absorption before treatment (sabins)
The chart below also can be used to determine the reduction of reverberant
noise level within a room due to changing the total room absorption.
For example, if the total amount of absorption in a space can be increased
from 700 to 2100 sabins, the reduction in reverberant noise level
NA will be about 5 dB. (See dot on chart scale at absorption ratio
of a = 2100/700 = 3.) Since absorption efficiencies vary with frequency,
the NR should be calculated at all frequencies for which sound absorption
coefficients are known.
Practical upper limit of improvement for most situations.
The NR is the reduction in reverberant noise level. This does not
affect the noise level very near the source of sound in a room. Also,
as indicated on the chart, a reduction in reverberant noise level
of 10 dB (an increase in absorption of greater than 10 times the initial
value before treatment) is the practical upper limit for most remedial
situations.
EXAMPLE PROBLEM (ROOM NOISE REDUCTION)
A small room 10 ft by 10 ft by 10 ft has all walls and floor finished
in ex posed concrete. The ceiling is completely covered with sound-absorbing
spray- on material. Sound absorption coefficients α are 0.02 for concrete
and 0.70 for spray-on material, both at 500 Hz.
Find the noise reduction NR in this room if sound-absorbing panels
are added to two adjacent walls. The sound absorption coefficient
a is 0.85 for panels at 500 Hz.
1. Compute the surface areas S.
S = 5 x 10 x 10=500 ft^2 of concrete
S = 10 X 10 = 100 ft^2 of spray-on material
2. Compute the total room absorption a with spray-on material on
the ceiling.
a1 = Σ S α = (500 X 0.02) + .(100 X 0.70) = 10 + 700 sabin’
3. Compute the total room absorption a2 with sound-absorbing panels
covering two walls and spray-on material on ceiling.
a2 = (300X 0.02) + (200X 0.85) + (100 X 0.70) = 6 + 170 + 70 = 246
sabin
4. Compute the noise reduction NR.
NR= 10log (a2÷a1) = 10log (246/80) = 10log (3.075 X 10^0)
= 10(0.4878) = 5dB
This would be a ‘noticeable improvement. With no treatment, the total
absorption in the room would only be 600 X 0.02 = 12 sabins. Therefore,
treating the ceiling alone provides
NR = 10 log (80/12)= 10 log 6.67 = 10(0.8241) = 8 dB
which is a “significant” reduction. However, initial conditions of
all hard surfaces in unfurnished rooms rarely occur.
Find the noise reduction NR if all four wall surfaces are treated
with fabric- covered panels and the floor is carpeted. The sound absorption
coefficient α of the carpet is 0.50 at 500 Hz.
1. Compute the total room absorption a3 with sound-absorbing panels
on all walls, spray-on material on ceiling, and carpet on floor.
a3 = Σ S α = (400X0.85) + (100 X0.70) + (100X0.50)
= 340 + 70 + 50 = 460 sabins
2. Compute the noise reduction NR for these improvements compared
to room conditions of spray-on ceiling treatment alone.
NR = 10log (a3/a1) = 10log(460/80) = 10 log (5.75 x 10^0)
= 10(0.7597) = 8 dB
Surfaces Treated ( addition to
ceiling) |
Room NR (at 500 Hz) |
Two walls
Four walls and floor |
5 dB
8 dB |
The results from both parts of the problem are summarized below.
Note: The NRs given in the above table would not be as great at low
frequencies be cause sound absorption coefficients usually are smaller
at low frequencies than at mid- or high frequencies.
NOISE REDUCTION FOR HIGH-NOISE ENVIRONMENTS
Low Ceiling, Machines Widely Spaced
In the example shown below, machines are widely spaced so that in
stalling efficient sound-absorbing treatment on the ceiling and upper
walls can reduce reverberant noise levels throughout the room. However,
the sound- absorbing treatment will be of little benefit to the individual
equipment operators in the free field because the direct sound energy
will reach the operator before it reaches the sound-absorbing materials.
High Ceiling, Machines Closely Spaced
In the example of closely spaced machines in a room with a high ceiling,
room surface treatment can be effective if reverberant noise levels
are higher than the free-field noise of some machines. A reduction
in reverberation will help make machine noise more directional (by
reducing the reflected sound), allowing workers to be more responsive
to their own machines. However, operators of closely spaced machines
may be in the free field of several machines, which would be unaffected
by ceiling and upper-wall treatment.
aa-72-1.jpg
Enclosure to Contain Machine Noise
The sound-isolating enclosure shown below can be designed to provide
noise reduction near the source so individual operators can be close
to their machines without experiencing high noise levels. Enclosures
can be designed with operable viewing panels to allow rapid access
when needed (see section 4 for sound-isolation principles, materials,
and constructions).
Note: Where noisy machines are located close to walls, sound-absorbing
wall treatment may provide useful noise reduction.
References
P. D. Emerson et al., Manual of Textile Industry Noise Control, Center
for Acoustical Studies, North Carolina State University, 1978 (contains
over 20 case studies).
P. Jensen et al., Industrial Noise Control Manual, U.S. Department
of Health, Education, and Welfare, December 1978 (contains over 60
case studies on a wide variety of industries).
R. B. Newman and W. J. Cavanaugh, “Design for Hearing,” Progressive
Architecture, May 1959.
W. G. Orr, Handbook for Industrial Noise Control, National Aeronautics
and Space Administration, NASA SP-5 108, 1981.
TRANSONDENT FACINGS
Sound-transparent facings (called transondent) may range from 5 to
50 percent or more open area, depending on absorption requirements.
Facings tend to reduce the effectiveness of sound-absorbing materials
by reflecting high-frequency sound waves. In general, the lower the
percentage of open area in the facing, the less absorption of high-frequency
sound energy. Sizes of holes, number of holes per unit area, and dimensions
of solid area between openings also affect the reduction in absorption.
Transondent facings such as perforated sheet metal, expanded metal,
or punched and pressed metal can be used alone in front of sound-absorbing
materials, or in combination with wood slats or other large-scale
protective elements.
Examples of open metal materials and a table of perforation sizes
and spacings for facing materials are shown below.
Note: When painting open facings, use rollers, not sprayers, to reduce
the likelihood that the openings will become blocked. Be careful also
to avoid using facings with very tiny holes which may easily become
clogged with paint.
Hole Diameter (in) |
Spacing (in oc) |
3/16
5/32
1/8
3/32
1/16
1/32 |
0.50*
0.40
0.30**
0.22**
0.15
0.08 |
* Do not exceed this spacing for hardboard material (e.g., pegboard).
** Most suitable for wall materials. Holes are small enough to discourage
jabbing with sharp objects and large enough so facing can be carefully
painted without becoming clogged.
Reference
W. R. Farrell, “Sound Absorption for Walls,” Architectural & Engineering
News, October 1965.
PERFORATED FACINGS
Perforated facings can be used to protect and conceal porous sound-
absorbing materials or, if highly transparent to sound waves, to conceal
sound- reflecting or diffusing surfaces. When used over a solid backup
surface without fuzz (fibrous materials) in the cavity, perforated
facings can act as multiple volume resonators to selectively absorb
sound with the individual holes sharing a common volume. Partitioned
(or subdivided) cavities can provide wider absorption near the resonant
frequency.
As shown by the graph below, the thinner the facing, the more efficient
the absorption of sound energy at mid- and high frequencies. The higher
the percentage of open area (from numerous, closely spaced perforations
to re duce size of solid areas), the more efficient the absorption
of sound energy at high frequencies. Sound transparency increases
as the size of the holes and number of holes per unit area increases,
and as the distance between holes decreases.
The critical frequency for circular perforations, above which sound
absorption efficiency drops off rapidly, can be found as follows:
fc = 40P/D
where fc = critical frequency (Hz)
P = open area (%)
D = hole diameter (in)
For example, 25 percent open perforated facing with 1/4-in-diameter
holes will have a critical frequency of
fc = 40 x 25 / 0.25 = 4KHz
Precise analysis should also take into account the thickness of the
facing and depth of the airspace behind the facing (cf., P. V. Brüel,
Sound Insulation and Room Acoustics, Chapman & Hall, London, 1951,
pp. 114-123).
Reference
T. J. Schultz, Acoustical Uses for Perforated Metals, Industrial
Perforators Association, Milwaukee, Wis., 1986, pp. 14-20.
PROTECTIVE FACINGS FOR WALL ABSORPTION
When absorption of high-frequency sound energy is not critical, the
open area of protective facings need only be greater than about 10
percent to control reverberation or noise buildup within rooms. As
a consequence, a wide variety of textures and forms can be used to
satisfy this requirement. When absorption is used to control echoes,
however, protective facings should have a higher percentage of open
area from numerous, closely spaced openings. To conceal the sound-absorbing
material behind most facings, tint the material black by spraying
with non-bridging water-base paint or use a dark sound- transparent
protective cover (e.g., burlap or open-weave fabric).
Reference
R. B. Newman and W. J. Cavanaugh, “Acoustics” in J. H. Callender
(ed.), Time-Saver Standards for Architectural Design Data, McGraw-Hill,
New York, 1966, p. 622.
RESONANT PANELS
Resonant panels are sound-absorbing panels which are designed to
pro vide low-frequency absorption ( 250 Hz). Example applications
for resonant panels are music practice rooms, radio/TV studios, and
the like. Resonant panels absorb energy from sound waves by vibrating
at a frequency deter mined by the geometry and damping characteristics
of the panel.
To decrease the resonant frequency, use wide spacings between supports
(> 2 ft), thin panel materials (e.g., plywood, hardboard), and
“deep” air space behind panels. To increase the resonant frequency,
use close spacings between supports, thick panel materials (or perforated,
thin panel materials with sound-absorbing material located close behind
the panel), and shallow or narrow airspace behind panels.
It is prudent to test unique resonant panel designs in reverberation
rooms to evaluate their performance. The resonant frequency fr
can be estimated by:
fr = 170 / sqr-rt(wd)
where fr. = resonant frequency (Hz)
w = surface weight of panel (lb/ft^2)
d = depth of airspace behind panel (in)
Reference
V. O. Knudsen and C. M. Harris, Acoustical Designing in Architecture,
Wiley, New York, 1950, p. 120 (paperback reprint is available from
the Acoustical Society of America, 500 Sunnyside Blvd., Woodbury,
NY 11797).
SUGGESTED SOUND-ABSORBING TREATMENT FOR ROOMS
Although the NRC rating method has the limitations presented earlier
in this section, it can be an adequate index to evaluate sound-absorbing
materials for use in treating the noncritical spaces listed below.
The last two groups in the table represent many of the spaces where
the NRC by itself does not pro vide sufficient information. Therefore,
special study may be required to deter mine the specific absorption
needs. For example, absorption for ceilings in open-plan offices,
where sound can reflect over partial-height barriers, destroying speech
privacy, should be evaluated only by noise isolation c/ass prime NIC’
ratings (see section 6), although a minimum NRC is given.
Type of Space |
Preferred NRCRange |
Ceiling Treatment |
Wall Treatment |
Private offices, large offices,
small conference rooms, hospitals, laboratory work spaces,
libraries, retail shops and stores |
0.65 to 0.75 |
Full |
None required |
Lobbies, corridors, gymnasiums |
0.65 to 0.75 |
Full |
Yes |
Secondary and college classrooms,
large meeting rooms |
0.65 to 0.75 |
partial |
Yes |
Kitchens, cafeterias, laundries,
restaurants |
|
Full |
Usually none required |
Computer equipment rooms, school
and industrial shops, machinery spaces |
> 0.75 |
Full |
yes |
Auditoriums, theaters, radio/TV
studios, music practice rooms, audiovisual facilities, churches,
courtrooms, chapels, mechanical equipment rooms, open-plan
schools, language laboratories, factories |
(These spaces in
particular require special study to determine the appropriate
type, amount, and location of sound-absorbing treatment.) |
Open offices |
> 0.80 |
Full |
Yes |
CHECKLIST FOR EFFECTIVE ABSORPTION OF SOUND
1. Apply sound-absorbing materials on surfaces that may contribute
to excessive reverberation, produce annoying echoes, or focus sound
energy. In auditoriums and similar facilities, use sound-absorbing
materials to control echoes and reverberation. Excessive reverberation
can seriously interfere with listening conditions, especially for
hearing-impaired and older persons. A doubling of the existing absorption
in a room will reduce the reverberation by one-half.
2. Do not use sound-absorbing materials on surfaces which should
provide useful sound reflections (e.g., above lecterns in auditoriums).
Sound-reflecting surfaces must have sound absorption coefficients
well below 0.20 and be properly shaped and oriented (see section 3).
3. Use sound-absorbing ceilings to control the buildup of noise within
rooms, un less the floor is carpeted and the room is filled with heavy
draperies and other sound-absorbing furnishings. Sound-absorbing materials
are commercially avail able that have a factory-applied surface finish
which is reasonably durable for ceiling applications as well as satisfying
appearance, light reflectance, and other architectural and fire safety
requirements.
4. Place absorption on the walls of very high rooms, small rooms,
or long and narrow rooms, where flutter echo may occur. In very large
rooms with low ceilings, wall absorption is rarely beneficial unless
needed to prevent flanking of sound energy around partial-height barriers
in open plans. Sound-absorbing wall panels that have a fabric finish
and hardened edges to maintain their shape are commercially available.
5. Be sure the mounting method used is best suited for the amount
of absorption desired. The actual method of mounting is important
because it will affect absorption efficiency. For example, sound-absorbing
materials directly attached with mechanical fasteners (mounting A)
are poor absorbers of low-frequency sound. However, when attached
to furring supports (mounting D), they will provide more absorption
at low frequencies; and when used in suspended ceiling systems (mounting
E), they can provide considerable low-frequency absorption. To achieve
maximum absorption from special sound-absorbing materials and units,
such as suspended baffles and spaced absorbers, install them at the
spacings recommended by manufacturers.
6. Do not overestimate the noise control benefits from sound absorption.
Re member, it takes a doubling of the existing absorption to achieve
only 3 dB of noise reduction! It requires an enormous increase in
existing absorption to achieve 6 dB of noise reduction. Consequently,
in most situations, 3 to 6 dB is the practical limit of noise reduction
benefits from adding sound absorption to rooms.
Next: (coming soon)
Prev: Optimum
Reverberation Time
top of page Home |